Shielded Twisted Pair Cable FTP, indoor, category 5, 2 pairs, solid, foil shield
Specifications:
Meets TIA /EIA-568-B.2 requirements
Fire protection - CM
|
Description:
Shielded Copper cable, 2 pairs, category 5, solid
Shield: aluminum foil
Cable is used for indoor horizontal installation
|
Materials:
Conductive material: wire made of soft annealed electrolytic copper
Conductor insulation: high-density polyethylene (HDPE)
The cable jacket: PVC
An aluminum tape shield is helically applied over the cable core with a minimum overlap of 25% or 5 mm
|
Technical characteristics:
|
Conductor diameter: 0.51 mm (24 AWG)
Insulated conductor diameter: 0,98 ± 0,02 mm
Outer cable diameter: 4,6 ± 0,2 mm
Jacket thickness: 0.4 mm
Minimum bend radius: 4 outer cable diameters
Conductor elongation: 14% minimum
Rip cord breaking strength: 10 kg
Drain wire diameter: 0.5 mm
Operating temperature: -40°C - +60°C
Standard package: 500 m
|
Electrical characteristics:
| Frequency, MHz |
RL |
Attenuation, dB |
NEXT, dB |
PSNEXT, dB |
ELFEXT, dB |
PSELFEXT, dB |
| 0,772 |
|
1,8 |
67,0 |
64,0 |
|
|
| 1,0 |
20,0 |
2,0 |
65,3 |
62,3 |
63,8 |
60,8 |
| 4,0 |
23,0 |
4,0 |
56,3 |
53,3 |
51,7 |
48,7 |
| 8,0 |
24,5 |
5,8 |
51,8 |
48,8 |
45,7 |
42,7 |
| 10,0 |
25,0 |
6,5 |
50,3 |
47,3 |
43,8 |
40,8 |
| 16,0 |
25,0 |
8,2 |
47,3 |
44,3 |
39,7 |
36,7 |
| 20,0 |
25,0 |
9,3 |
45,8 |
42,8 |
37,7 |
34,7 |
| 25,0 |
24,3 |
10,4 |
44,3 |
41,3 |
35,8 |
32,8 |
| 31,25 |
23,6 |
11,7 |
42,9 |
39,9 |
33,9 |
30,9 |
| 62,5 |
21,5 |
17,0 |
38,4 |
35,4 |
27,8 |
24,8 |
| 100,0 |
20,1 |
22,0 |
35,3 |
32,3 |
23,8 |
20,8 |
| Max conductor resistance at 20°C |
9.38 Ohm/100 m |
| Max Resistance Unbalance |
5% |
| Max pair-to-ground capacitance unbalance |
330 pF /100 m |
| Characteristic Impedance at 0.772-100 MHz |
85-115 Ohm |
| Mutual capacitance |
5.6 nF/m |
| Spark Test |
2.5 kV |
Ordering:
| FTP2-C5E-SOLID-INDOOR |
Shielded Twisted Pair Cable FTP, 2 pairs, solid, indoor, category 5 |
|
|
|