Catalog

Shielded Twisted Pair Cable FTP, 10/25/50/100 pairs, Solid, Outdoor (Category 3)

Shielded Twisted Pair Cable FTP, category 3, 10/25/50/100 pairs, solid, outdoor
Specifications:
Meets EIA/TIA 568-B.2 for category 3 requirements
Fire protection – CMX
The cable meets IEC 60332-1 fire safety standard

Description:
Shielded Copper cable, 10/25/50/100 pairs, category 3, solid
Shield – aluminum foil
Cable is used for outdoor installation

Materials:
Conductive material: wire made of soft annealed electrolytic copper
Conductor insulation: HDPE
The cable jacket: UV resistant black PE
An aluminum tape shield is helically applied over the cable core with a minimum overlap of 25% or 5 mm (0.19")

Electrical characteristics:
Max DC Resistance at 20°C (68°F) 9.38 Ohm/100 m (2.86 Ohm/100 ft)
Max Resistance Unbalance 5%
Max Capacitance unbalance pair-to-ground at 1kHz 330 pF/100 m (100.58 pF/ 100ft)
Characteristic Impedance at 1-16 MHz 85-115 Ohm
Min worst pair Structural Return Loss (SRL)
at 10 MHz
at 16 MHz

12 dB
10 dB
Max attenuation at 20°C (68°F)
at 64 kHz
at 256 kHz
at 512 kHz
at 772 kHz
at 1 MHz
at 4 MHz
at 8 MHz
at 10 MHz
at 16 MHz

0.9 dB/100 m (0.27 dB/100 ft)
1.3 dB/100 m (0.40 dB/100 ft)
1.8 dB/100 m (0.55 dB/100 ft)
2.2 dB/100 m (0.67 dB/100 ft)
2.6 dB/100 m (0.79 dB/100 ft)
5.6 dB/100 m (1.70 dB/100 ft)
8.5 dB/100 m (2.59 dB/100 ft)
9.7 dB/100 m (2.96 dB/100 ft)
13.1 dB/100 m (3.99 dB/100 ft)
Min worst pair to pair NEXT loss
at 772 kHz
at 1 MHz
at 4 MHz
at 8 MHz
at 10 MHz
at 16 MHz

43 dB
41 dB
32 dB
27 dB
26 dB
23 dB
Min Relative Velocity of Propagation at 10 MHz 0.585


10 pairs


1 – Jacket
2 – Rip-cord
3 – Shield-foil
4 – Drain wire
5 – Protective skin
6 – Polymer tape
7 – Solid twisted pair
Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 8 mm (0.31")
Jacket thickness: 1 mm (0.039")
Maximum strand pitch: 150 mm (5.9")
Minimum bend radius: 10 outer cable diameters
Conductor elongation: 14% minimum
Rip cord has a breaking strength of 10 kg (98 N)
Drain wire diameter: 0.5 mm (0.019")
Operating temperature: -40°C – +70°C (-40°F – +158°F)
Weight per 1000 ft (304.8 m): 19.5 kg (43 lbs)
Standard package: 1000 m (3280 ft)


25 pairs


1 – Jacket
2 – Rip-cord
3 – Shield-foil
4 – Drain wire
5 – Protective skin
6 – Polymer tape
7 – Solid twisted pair
Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 12 mm (0.47")
Jacket thickness: 1 mm (0.039")
Maximum strand pitch: 150 mm (5.9")
Minimum bend radius: 10 outer cable diameters
Conductor elongation: 14% minimum
Rip cord has a breaking strength of 10 kg (98 N)
Drain wire diameter: 0.5 mm (0.019")
Operating temperature: -40°C – +70°C (-40°F – +158°F)
Weight per 1000 ft (304.8 m): 100.1 kg (45.4 lbs)
Standard package: 1000 m (3280 ft)


50 pairs


1 – Jacket
2 – Rip-cord
3 – Shield-foil
4 – Drain wire
5 – Protective skin
6 – Polymer tape
7 – Solid twisted pair
Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 15 mm (0.59")
Jacket thickness: 1 mm (0.039")
Maximum strand pitch: 150 mm (5.9")
Minimum bend radius: 10 outer cable diameters
Conductor elongation: 14% minimum
Rip cord has a breaking strength of 10 kg (98 N)
Drain wire diameter: 0.5 mm (0.019")
Operating temperature: -40°C – +70°C (-40°F – +158°F)
Weight per 1000 ft (304.8 m): 191.5 kg (86.9 lbs)
Standard package: 500 m (1640 ft)


100 pairs


1 – Jacket
2 – Rip-cord
3 – Shield-foil
4 – Drain wire
5 – Protective skin
6 – Polymer tape
7 – Solid twisted pair
Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 15 mm (0.59")
Jacket thickness: 1 mm (0.039")
Maximum strand pitch: 150 mm (5.9")
Minimum bend radius: 10 outer cable diameters
Conductor elongation: 14% minimum
Rip cord has a breaking strength of 10 kg (98 N)
Drain wire diameter: 0.5 mm (0.019")
Operating temperature: -40°C – +70°C (-40°F – +158°F)
Weight per 1000 ft (304.8 m): 155.4 kg (342.7 lbs)
Standard package: 500 m (1640 ft)

Ordering:
FTPXX-C3-SOLID-OUTDOOR Shielded Twisted Pair Cable (FTP), 10/25/50/100 pairs, solid, outdoor, category 3

XX – pair quantity: 10, 25, 50, 100