Catalog

Unshielded Twisted Pair Cable (UTP), 10/25/50/100 pairs, Solid, Indoor (Category 3)

Twisted Pair Cable UTP, 10/25/50/100 pairs, category 3, solid
Specifications:
Meets EIA/TIA 568-B for category 3 requirements
Fire protection – IEC60332-1 (CM)
The cable meets IEC 60332-1 fire safety standard

Description:
Unshielded Copper cable, 10/25/50/100 pairs, category 3, solid.
Cable is used for indoor installation

Materials:
Conductive material: soft annealed electrolytic copper
Conductor insulation: HDPE
The cable jacket: PVC

Electrical characteristics:
Max DC Resistance at 20°C (68°F) 9.38 Ohm/100 m (2.9 Ohm/100 ft)
Max Resistance Unbalance 3%

Max Capacitance unbalance – pair-to-ground at 1kHz

330 pF/100 m (101 pF/100 ft)
Characteristic Impedance at 1-16 MHz 85-115 Ohm
Min worst pair Structural Return Loss (SRL)
Up to 10 MHz
At 16 MHz

12 dB
10 dB
Max attenuation at 20°C (68°F) and
At 772 kHz
At 1 MHz
At 4 MHz
At 8 MHz
At 10 MHz
At 16 MHz

2.2 dB/100 m (0.67 dB/100 ft)
2.6 dB/100 m (0.79 dB/100 ft)
5.6 dB/100 m (1.70 dB/100 ft)
8.5 dB/100 m (2.59 dB/100 ft)
9.7 dB/100 m (2.96 dB/100 ft)
13.1 dB/100 m (3.99 dB/100 ft)
Min worst pair to pair NEXT loss at 772 kHz
At 1 MHz
At 4 MHz
At 8 MHz
At 10 MHz
At 16 MHz

43 dB
41 dB
32 dB
27 dB
26 dB
23 dB

Min Relative Velocity of Propagation at 10 MHz

0,585


10 pairs

Twisted Pair Cable UTP, 10 pairs, category 3, solid
Twisted Pair Cable (UTP) 10 pairs 1 – Jacket
2 – Rip-cord
3 – Protective skin
4 – Polymer tape
5 – Solid twisted pair
Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 7.5 mm (0.29")
Jacket thickness: 1.0 mm (0.039")
Maximum strand pitch: 100 mm (3.93")
Minimum bend radius: 6 outer cable diameters
Conductor elongation: 14% minimum
Operating temperature: -10°C – +50°C (+14°F – +122°F)
Weight per 1000 ft (304.8 m): 19.5 kg (43 lbs)
Standard package: 1000 m (3280 ft)


25 pairs

Twisted Pair Cable UTP, 25 pairs, category 3, solid
Twisted Pair Cable (UTP) 25 pairs 1 – Jacket
2 – Rip-cord
3 – Protective skin
4 – Polymer tape
5 – Solid twisted pair
Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 11 mm (0.43")
Jacket thickness: 1.0 mm (0.039")
Maximum strand pitch: 100 mm (3.93")
Minimum bend radius: 6 outer cable diameters
Conductor elongation: 14% minimum
Operating temperature: -10°C – +50°C (+14°F – +122°F)
Weight per 1000 ft (304.8 m): 46.6 kg (102.8 lbs)
Standard package: 1000 m (3280 ft)


50 pairs

Twisted Pair Cable UTP, 50 pairs, category 3, solid
Twisted Pair Cable (UTP) 50 pairs 1 – Jacket
2 – Rip-cord
3 – Protective skin
4 – Polymer tape
5 – Solid twisted pair
Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 15 mm (0.59")
Jacket thickness: 1.0 mm (0.039")
Maximum strand pitch: 150 mm (5.9")
Minimum bend radius: 8 outer cable diameters
Conductor elongation: 14% minimum
Operating temperature: -10°C – +50°C (+14°F – +122°F)
Weight per 1000 ft (304.8 m): 89.3 kg (196.9 lbs)
Standard package: 500 m (1640 ft)


100 pairs


Twisted Pair Cable (UTP) 100 pairs 1 – Jacket
2 – Rip-cord
3 – Protective skin
4 – Polymer tape
5 – Solid twisted pair
Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 200 mm (0.78")
Jacket thickness: 1.0 mm (0.039")
Maximum strand pitch: 150 mm (5.9")
Minimum bend radius: 8 outer cable diameters
Conductor elongation: 14% minimum
Operating temperature: -10°C – +50°C (+14°F – +122°F)
Weight per 1000 ft (304.8 m): 169.2 kg (372.9 lbs)
Standard package: 500 m (1640 ft)

Ordering:
UTPXX-C3-SOLID-INDOOR Unshielded Twisted Pair Cable UTP, 10/25/50/100 pairs, solid, indoor, category 3
UTP100-C3-SOLID-INDOOR-HFFR Unshielded Twisted Pair Cable UTP, 100 pairs, solid, indoor, category 3, halogenfree, fire resistant jacket

XX – quantity of pairs: 10, 25, 50, 100 pairs