Catalog

Twisted Pair Cable (UTP), 25 pairs (4x6 +1), Category 5, Solid, Indoor, PVC

1 - Copper Conductor
2 - HDPE Insulation
3 - Identification Tape
4 - Polyester
5 - Ripcord
6 - Outer Jacket
7 - Inner Jacket

Specifications:
Meets TIA/EIA 568 requirements
Fire protection - CM
The cable meets UL 444 UL 1581 fire safety standard

Description:
Unshielded multi-pair copper cable, 25 pairs, category 5, solid. Cable consists of 6 unshielded (UTP) bunches of 4 twisted pairs each, and 1 central unshielded twisted pair (4 x 6 + 1)
Application: Horizontal communication cable
Cable is used PVC jacket installation

Materials:
Conductive material: wire made of annealed bare copper
Conductor insulation: HDPE
The cable jacket: PVC

Technical characteristics:
Conductor diameter: 0.51 mm (0.02") (24 AWG x 25P)
Insulated conductor diameter: 0.88 mm (0.035")
Outer cable diameter: 13 mm (0.51")
Jacket thickness: 0.8 mm (0.031")
Minimum bend radius: 10 outer cable diameters
Conductor elongation: 15% minimum
Rip cord has a breaking strength of 15.3 kg (150 N)
Operating temperature: -20C - +75C (-4F - +167F)
Weight per 1000 ft (304.8 m): 54.9 kg (120.9 lbs)
Standard package: 500 m (1640 ft)

Electrical characteristics
Frequency, MHz RL Attenuation, dB NEXT, dB PSNEXT, dB ELFEXT, dB PSELFEXT, dB
1.0 17.0 2.0 65.3 62.3 61.0 61.0
4.0 18.8 4.1 56.3 53.3 49.0 49.0
10.0 20.0 6.5 47.3 47.3 41.0 41.0
16.0 20.0 8.2 44.2 44.2 37.0 37.0
20.0 20.0 9.3 39.9 42.8 35.0 35.0
31.25 18.6 11.7 35.4 39.9 31.0 31.0
62.5 16.5 17.0 32.3 35.4 25.0 25.0
100.0 15.1 22.0 42.9 32.3 21.0 21.0


Characteristic Impedance at 0.772-100 MHz 100 15 Ohm
DC Resistance Unbalance 5%
Pair-to-Ground Capacitance Unbalance 330 pF/100 m (101 pF/100 ft)
Conductor resistance at 20C (68F) 9.38 Ohm/100 m (2.86 Ohm/100 ft)
Mutual Capacitance 5.6 nF/m (1.7 nF/ft)
Spark Test 2.5 kV

Ordering
UTP25W-C5-SOLID-INDOOR-PVC Unshielded twisted pair cable (UTP), 25 pairs (4x6 +1), category 5, solid, indoor, PVC